APPLICATION
Type SE, service entrance cable is primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard; however, the cable may be used in all applications where Type SE cable is permitted. SER may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating is 600 volts.
PRODUCT FEATURES
- Type SE cable is constructed with AA-8000 series aluminum alloy, compact stranded conductors.
- Cross-linked polyethylene insulation rated for a maximum operation temperature of 90°C in wet and dry locations.
- Eco friendly sunlight resistant, flame retardant and heavy metal free Polyvinyl Chloride (PVC) Jacket.
- Insulation and Jacket materials are in compliance with RoHS, Directive 2002/95/EC.
- Sequential foot markings for easier inventory control management.
STANDARDS & REFERENCESType SE cable complies with :• ASTM- All applicable standards• UL Standard 44 for XHHW-2 conductors• UL Standard 83 for THHN/THWN conductors• UL Standard 854• Federal Specification A-A-59544• National Electrical Code, NFPA 70. 2011 Edition• RoHS/ REACHCONSTRUCTIONConductor: compact copper or AA-8000 series aluminum alloy, compact strandedInsulation:Cross-linked polyethylene(XLPE) insulation with property of heat.Moistrure and abrasion resistance and flame retardant.Sheath:sunlight resistant gray polyvinyl chloride (PVC).Type SE cable is constructed with sunlight resistant Type XHHW-2 conductors or Type THHN/THWN conductors.Cable assembly plus reinforcement tape are jacketed with sunlight resistant gray polyvinyl chloride (PVC). Available as 1 conductor with a concentric ground, 2 conductor with a round or concentricground, or 3 conductor with a bare ground. SE cable is jacketed with gray sunlight resistant polyvinyl chloride (PVC).Aluminum Specifications:Service Entrance Cable Style R (SER) - 2 Conductor with Ground SER |
Size AWG & Construction | Stranding | Nominal | Weight per | Ampacity (AMPS) * |
Diameter | 1000 ft. |
Phase | Equipment Ground | (in) | (lbs) | 90˚ C | Dwelling |
Conductors | Conductor | | |
6-6-6 | 7 | - | 0.65 | 150 | 60 | - |
4-4-6 | 7 | - | 0.681 | 196 | 75 | - |
4/4/4 | 7 | - | 0.682 | 196 | 75 | - |
|
Service Entrance Cable Style R (SER) - 3 Conductor with Ground SER |
Size AWG & Construction | Stranding | Nominal | Weight per | Ampacity (AMPS) * |
Diameter | 1000 ft. |
Phase | Equipment Ground | (in) | (lbs) | 90˚ C | Dwelling |
Conductors | Conductor | | |
8-8-8-8 | Solid | Solid | 0.588 | 128 | 45 | - |
6-6-6-6 | 7 | 7 | 0.684 | 180 | 60 | - |
4-4-4-6 | 7 | 7 | 0.754 | 240 | 75 | - |
2-2-2-4 | 7 | 7 | 0.893 | 344 | 100 | 100 |
1-1-1-3 | 19 | 7 | 1.003 | 432 | 115 | 110 |
1/0-1/0-1/0-2 | 19 | 7 | 1.097 | 521 | 135 | 125 |
2/0-2/0-2/0-1 | 19 | 19 | 1.197 | 633 | 150 | 150 |
3/0-3/0-3/0-1/0 | 19 | 19 | 1.314 | 771 | 175 | 175 |
4/0-4/0-4/0-2/0 | 19 | 19 | 1.443 | 942 | 205 | 200 |
250-250-250-3/0 | 37 | 19 | 1.601 | 1106 | 230 | 225 |
|
Service Entrance Cable Style R (SER) - 4 Conductor with Ground SER |
Size AWG & Construction | Stranding | Nominal | Weight per | Ampacity (AMPS) * |
Diameter | 1000 ft. |
Phase | Equipment Ground | (in) | (lbs) | 90˚ C | Dwelling |
Conductors | Conductor | | |
2-2-2-2-4 | 7 | 7 | 1.004 | 450 | 100 | 100 |
2/0-2/0-2/0-2/0-1 | 19 | 19 | 1.346 | 824 | 150 | 150 |
4/0-4/0-4/0-4/0-2/0 | 19 | 19 | 1.621 | 1226 | 205 | 200 |
250-250-250-250-3/0 | 37 | 19 | 1.95 | 1454 | 230 | 225 |
1. Data are approximate and subject to normal manufacturing tolerances.
2. Standard lengths are subject to normal manufacturing tolerance of +/- 10%
3. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
4. Table values reflect XHHW-2 aluminum conductors
5.Package:A-500' B-2,500' C-1,000' D-5,000'
UL Certificate for XHHW,SER,SEU,MC Cable