Dzl &Szl Series Coal Fired Hot Water Boiler

Structure
Fire Tube
Media
Hot Water
Water Circulation
Forced Circulation
Drum Placement
Horizontal Boiler
Pressure
Low Pressure
Manufacturing Level
A
Burning Style
Chamber Combustion Boiler
Usage
Industrial
Transport Package
Naked by 40′ Ot or Flat Rack Containers
Trademark
QD Hammer
Origin
Qingdao
HS Code
84021900
Production Capacity
10sets/Month
Reference Price
$ 9,000.00 - 180,000.00

Product Description

DZL Series Hot Water Boiler Specification
  The DZL series easy installation steam boiler is the most advanced water-fire 
tube boiler in China, which is strong, high efficiency, but with small installation space, long life.
 
Main Features of DZL boiler

1.High temperature annealing treatment of Arched tube plate
2.Fully automated tube sheet welding
3.1.4 times' hydro test
4.All-around crack detection
5.Optimized installation technique after 20 years
6.24 hours operation debugging of grate
7.60 lines inspection before delivery
8.Fully automated processing of spirally corrugated tube

Dzl &Szl Series Coal Fired Hot Water Boiler
The ameliorated boiler uses the wing smoke flue, one-way threaded smoke pipe, 
arch tube sheet, smoke-gas segregation room, and several other advanced technologies so that the boiler bearing condition could be ameliorated, the circulating water flow speed could be improved and the safety coefficient could be enhanced.
  This series boiler is well designed, compactly made-up, quickly installed, mono layer, so that the civil engineering and the investment could be saved. This amelioration, which extends the boiler's working life and is the national energy saving product, makes great contribution to the further development of boiler, it sets the pace in china and fill up the national margin.
   Boiler Model    DZL1.4-0.7/95/70-AIIDZL2.8-0.7/95/70-AIIDZL4.2-1.0/
115/70-AII
DZL5.6-1.0/
115/70-AII
DZL7.0-1.0/
115/70-AII
DZL14-1.25/
115/70-AII
Rated Evaporation CapacityMW1.42.84.25.67.014
Operation PressureMpa0.70.71.01.01.01.25
Steam TemperatureºC9595115115115115
Water-inlet TemperatureºC707070707070
Boiler Heating Efficiency%≥76.6≥78.8≥79≥82≥82≥83
Area of StokerM23.045.147.411.411.420.8
Coal Available II type bitumite, low heat capability:17700-21000KJ/kg 
Water Pump Model IS80-65-160IS100-80-160IS125-100-200IS125-100-200IS125-100-200IS125-100-250
Motor PowerKW7.51530455575
Blast Fan Model G6-41-13
NO5.4A
G6-41-13
NO6.4A
G6-41-13
NO7.1A
G6-41-13
NO8.5A
G6-41-13
NO8.5A
TG20-1
Ventilation m3/h4358-23107358-359610354-539418137-936918137-936732079
Wind PressurePa994-12541181-14361697-22702535-33912535-33912559
Motor PowerKW35.57.518.518.537
Induced Draft FanModel Y6-41-13
NO5.4C
Y6-41-13
NO7.1C
1Y6-41-13
NO10C
Y6-41-13
NO11.2D
Y6-41-13
NO11.2D
GY20-15
Ventilationm3/h8901-435015219-817132144-1660741773-2157841773-2157873308
Wind PressurePa2568-32402454-32832574-34442764-36972764-36973515
Motor PowerKW1122374555110
Dimensions of Biggest Parts for ShipmentM5.82×2.26×3.226.51×2.6×3.527.5×2.9×3.57.1×3.2×3.57.5×3.2×3.59.1×2.4×3.55
Weight of Biggest Parts for ShipmentT192835374030
Remark: This parameter is just for reference, for exact parameter, suject to our drawings.

Dzl &Szl Series Coal Fired Hot Water Boiler
SZL Series Hot Water Boiler Specification
  SZL water tube easy installation(assembled) boiler has 2 vertical steam drums, and the innovative horizontal cyclone-fired combustion chamber, which could effectively enhance the thermal efficiency and reduce the flue gas emission concentration. The flue gas emission  concentration is lower than 100 mm/nm3, the flue gas blackness is lower than Ringelmann level 1,which enables the boiler to be used in the first-class environment protected area.
The boiler installs one cast iron economizer at its back body, the fire-gate applies the chamber-segregated ventilation structure, which is easy to adjust. The separate-layer coal supply device could be chosen according to the customer requirement. Advantages of such boiler are: strong power, high thermal efficiency, 110% override capability,
compactly designed, small floor area.
Dzl &Szl Series Coal Fired Hot Water Boiler

Dzl &Szl Series Coal Fired Hot Water BoilerDzl &Szl Series Coal Fired Hot Water Boiler
Boiler ModelSZL4.2-1.0/
95/70-AII
SZL5.6-1.0/
95/70-AII
SZL7.0-1.0./
115/70-AII
SZL10.5-1.25/
115/70-AII
SZL14-1.25/
130/70-AII
Rated Evaporation CapacityMW4.25.67.010.514
Operation PressureMpa1.01.01.01.251.25
Steam TemperatureºC9595115115130
Water-inlet TemperatureºC7070707070
Heating Efficiency %≥80≥80≥80≥81≥82
Area of Stoker M27.158.611.7216.418.9
Coal Available II type bitumite,low heat capability:17700-21000KJ/kg
Water PumpModel IS125-100-
200
IS125-100-
200
IS125-100-
250
IS125-100-
250
IS200-150-
315
Motor PowerKW3045557575
Blast FanModel G6-41-13
NO7.1A
G6-41-13
NO8.5A
G6-41-13
NO8.5A
TG15-1TG20-1
Ventilation m3/h5349-103549369-181379369-181372300032079
Wind PressurePa1697-22702535-33912535-339119602559
Motor PowerKW7.518.518.52237
Induced Draft FanModel Y6-41-13
NO10C
Y6-41-13
NO11.2D
Y6-41-13
NO11.2D
TY15-2GY20-15
Ventilationm3/h32144-
16604
41773-
21578
41773-
21578
4000073308
Wind PressurePa2575-34442764-36972764-369730383515
Motor PowerKW37454575110
Dimensions of Biggest Parts for ShipmentM7.62×3.27×
3.46
8.82×3.34×
3.46
8.0×3.5×2.79.05×3.35×
3.69
10.6×3.35×
3.69
Weight of Biggest Parts for ShipmentT3145282427
Remark: This parameter is just for reference, for exact parameter, suject to our drawings

.

 

 

PTSINDIA.NET, 2023