Boiler Model | DZL1.4-0.7/95/70-AII | DZL2.8-0.7/95/70-AII | DZL4.2-1.0/ 115/70-AII | DZL5.6-1.0/ 115/70-AII | DZL7.0-1.0/ 115/70-AII | DZL14-1.25/ 115/70-AII | |||
Rated Evaporation Capacity | MW | 1.4 | 2.8 | 4.2 | 5.6 | 7.0 | 14 | ||
Operation Pressure | Mpa | 0.7 | 0.7 | 1.0 | 1.0 | 1.0 | 1.25 | ||
Steam Temperature | ºC | 95 | 95 | 115 | 115 | 115 | 115 | ||
Water-inlet Temperature | ºC | 70 | 70 | 70 | 70 | 70 | 70 | ||
Boiler Heating Efficiency | % | ≥76.6 | ≥78.8 | ≥79 | ≥82 | ≥82 | ≥83 | ||
Area of Stoker | M2 | 3.04 | 5.14 | 7.4 | 11.4 | 11.4 | 20.8 | ||
Coal Available | II type bitumite, low heat capability:17700-21000KJ/kg | ||||||||
Water Pump | Model | IS80-65-160 | IS100-80-160 | IS125-100-200 | IS125-100-200 | IS125-100-200 | IS125-100-250 | ||
Motor Power | KW | 7.5 | 15 | 30 | 45 | 55 | 75 | ||
Blast Fan | Model | G6-41-13 NO5.4A | G6-41-13 NO6.4A | G6-41-13 NO7.1A | G6-41-13 NO8.5A | G6-41-13 NO8.5A | TG20-1 | ||
Ventilation | m3/h | 4358-2310 | 7358-3596 | 10354-5394 | 18137-9369 | 18137-9367 | 32079 | ||
Wind Pressure | Pa | 994-1254 | 1181-1436 | 1697-2270 | 2535-3391 | 2535-3391 | 2559 | ||
Motor Power | KW | 3 | 5.5 | 7.5 | 18.5 | 18.5 | 37 | ||
Induced Draft Fan | Model | Y6-41-13 NO5.4C | Y6-41-13 NO7.1C | 1Y6-41-13 NO10C | Y6-41-13 NO11.2D | Y6-41-13 NO11.2D | GY20-15 | ||
Ventilation | m3/h | 8901-4350 | 15219-8171 | 32144-16607 | 41773-21578 | 41773-21578 | 73308 | ||
Wind Pressure | Pa | 2568-3240 | 2454-3283 | 2574-3444 | 2764-3697 | 2764-3697 | 3515 | ||
Motor Power | KW | 11 | 22 | 37 | 45 | 55 | 110 | ||
Dimensions of Biggest Parts for Shipment | M | 5.82×2.26×3.22 | 6.51×2.6×3.52 | 7.5×2.9×3.5 | 7.1×3.2×3.5 | 7.5×3.2×3.5 | 9.1×2.4×3.55 | ||
Weight of Biggest Parts for Shipment | T | 19 | 28 | 35 | 37 | 40 | 30 |
Boiler Model | SZL4.2-1.0/ 95/70-AII | SZL5.6-1.0/ 95/70-AII | SZL7.0-1.0./ 115/70-AII | SZL10.5-1.25/ 115/70-AII | SZL14-1.25/ 130/70-AII | ||
Rated Evaporation Capacity | MW | 4.2 | 5.6 | 7.0 | 10.5 | 14 | |
Operation Pressure | Mpa | 1.0 | 1.0 | 1.0 | 1.25 | 1.25 | |
Steam Temperature | ºC | 95 | 95 | 115 | 115 | 130 | |
Water-inlet Temperature | ºC | 70 | 70 | 70 | 70 | 70 | |
Heating Efficiency | % | ≥80 | ≥80 | ≥80 | ≥81 | ≥82 | |
Area of Stoker | M2 | 7.15 | 8.6 | 11.72 | 16.4 | 18.9 | |
Coal Available | II type bitumite,low heat capability:17700-21000KJ/kg | ||||||
Water Pump | Model | IS125-100- 200 | IS125-100- 200 | IS125-100- 250 | IS125-100- 250 | IS200-150- 315 | |
Motor Power | KW | 30 | 45 | 55 | 75 | 75 | |
Blast Fan | Model | G6-41-13 NO7.1A | G6-41-13 NO8.5A | G6-41-13 NO8.5A | TG15-1 | TG20-1 | |
Ventilation | m3/h | 5349-10354 | 9369-18137 | 9369-18137 | 23000 | 32079 | |
Wind Pressure | Pa | 1697-2270 | 2535-3391 | 2535-3391 | 1960 | 2559 | |
Motor Power | KW | 7.5 | 18.5 | 18.5 | 22 | 37 | |
Induced Draft Fan | Model | Y6-41-13 NO10C | Y6-41-13 NO11.2D | Y6-41-13 NO11.2D | TY15-2 | GY20-15 | |
Ventilation | m3/h | 32144- 16604 | 41773- 21578 | 41773- 21578 | 40000 | 73308 | |
Wind Pressure | Pa | 2575-3444 | 2764-3697 | 2764-3697 | 3038 | 3515 | |
Motor Power | KW | 37 | 45 | 45 | 75 | 110 | |
Dimensions of Biggest Parts for Shipment | M | 7.62×3.27× 3.46 | 8.82×3.34× 3.46 | 8.0×3.5×2.7 | 9.05×3.35× 3.69 | 10.6×3.35× 3.69 | |
Weight of Biggest Parts for Shipment | T | 31 | 45 | 28 | 24 | 27 |