| Voltage (automatic range): | 15 ~ 400V ± (reading × 0.2% + 3 words) ± 0.04% (range) |
| Current (automatic range): | 0.10 ~ 20A ± (reading × 0.2%+3 words) ± 0.04% (range) |
| Power: | COS Φ > 0.15 ± (reading × 0.5% +3 words) |
| Frequency (power frequency): | 45 ~ 65(Hz) Measurement accuracy: ± 0.1% |
| Short circuit impedance: | 0 ~ 100% Measurement accuracy: ± 0.5% |
| Repeat stability: | ratio difference < 0.2%, angle difference < 0.02 ° |
| Display: | 5 digits |
| Protection current: | the test current is greater than 18A, the internal relay of the instrument is disconnected, and overcurrent protection is provided. |
| Environment temperature: | -10 ºC~ 40 ºC |
| Relative humidity: | ≤ 85%RH |
| Power supply: | AC 220V±10% 50Hz±1Hz |
| Dimensions: |
Tester: 360*290*170 (mm)
Wire box: 360*290*170 (mm) |
| Weight: |
Tester: 4.85Kg
Wire box: 5.15KG |