| No. | DETAIL | UNITS | DATA |
| Type | 11kV gapless type metal oxide surge arrester - Distribution class | ||
| 1. | Nominal system voltage | kV | 11 |
| 2. | Highest system voltage | kV | 12 |
| 3. | Basic Insulation Level (BIL) | kV | 95 |
| 3. Ratings and type of surge arrester | |||
| 4. | Specification to which surge arrester complies | IEC 60099-4 | |
| 5. | Rated voltage of surge arrester | kV | 10 |
| 6. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA | 10 |
| 7. | Maximum continuous operating voltage of surge arrester | kV | 7.3 |
| 8. | Gapless or gapped type metal-oxide surge arrester | Gapless | |
| 9. | Material of insulation | High temperature vulcanised silicon rubber | |
| 10. | Rated frequency of surge arrester | Hz | 50 |
| 11. | Design altitude of surge arrester (above sea level) | m | 1 400m |
| 12. | Design ambient temperature of surge arrester | oC | -1 to40 |
| 13. | Specific creepage distance of surge arrester | .mm/kV | 25 |
| Automatic earth lead disconnectors requirements | |||
| 14. | Automatic earth lead disconnectors to be fitted | Yes/No | YES |
| 15. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade | To SABS 763, 316 | |
| Tests | |||
| 16. | Previous type test results/certificate to be provided with bid | Yes/No | Yes |
| 17. | Routine test results/certificate to be provided on delivery | Yes/No | Yes |
| 18. | Drawing showing dimensions of the arrestor to be provided with the bid | Yes/No | Yes |
| 19. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing | kV | 28 |
| 20. | Maximum steep current impulse residual voltage for a 10 kA, 1/20 µs, discharge current | kV | 50 |
| 21. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current | kV | 40 |
| 22. | Lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing | kV | 95 |
| 23. | Line discharge class rating | 1 | |
| 24. | Long duration current, 2 000 µs, impulse withstand | A | 250 A |
| 25. | High current, 4/10 µs, impulse withstand | kA | 100 kA |
| 26. | Automatic earth lead disconnector to be tested in accordance with IEC 60099-4 | Yes/No | Yes |
| S/N | TECHNICAL DETAILS | UNITS | DATA | |
| 1. | Type | 33kV gapless type metal oxide surge arrester - Distribution class | ||
| 2. | Nominal system voltage | kV | 33 | |
| 3. | Highest system voltage | kV | 36 | |
| 4. | Power frequency | Hz | 50 | |
| 5. | Basic Insulation Level (BIL) | kV | 170 | |
| 3. Ratings and type of surge arrester | ||||
| 6. | Specification to which surge arrester complies | IEC 60099 | ||
| 7. | Rated voltage of surge arrester | kV | 29 | |
| 8. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA | 10 | |
| 9. | Maximum continuous operating voltage of surge arrester | kV | 22 | |
| 10. | Gapless or gapped type metal-oxide surge arrester | Gapless | ||
| 11. | Insulation Material | Silicon rubber | ||
| 12. | Cantilever strength of surge arrester | Nm | 300 | |
| 13. | Rated frequency of surge arrester | Hz | 50 | |
| 14. | Design altitude of surge arrester (above sea level) | m | 1 400m | |
| 15. | Design ambient temperature of surge arrester | oC | -1 to 40 | |
| 16. | Minimum phase-to-ground specific creepage distance of surge arrester | .mm/kV | 25 | |
| Automatic earth lead disconnectors requirements | ||||
| 17. | Automatic earth lead disconnectors fitted | Yes/No | Yes | |
| 18. | Corrosion protection of metal and alloy parts: galvanising | To SABS 763, 316 | ||
| specification and/or stainless steel grade | |||
| Tests | |||
| 19. | Previous Type Test reports/certificate from recognized authority to be provided with bid | Yes/No | Yes |
| 20. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing | kV | 70 |
| 21. | Maximum steep current impulse residual voltage for a 10 kA, 1/20 µs, discharge current | kV | 99.7 |
| 22. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current | kV | 91.8 |
| 23. | Lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing | kV | 170 |
| 24. | Line discharge class rating | Class | 1 |
| 25. | Long duration current, 2 000 µs, impulse withstand | A | 250 A |
| 26. | High current, 4/10 µs, impulse withstand | kA | 100 kA |
| 27. | Is the automatic earth lead disconnector tested in accordance with IEC 60099-4? | Yes/No | Yes |
| S/N | TECHNICAL DETAILS | UNITS | DATA |
| 1. | Description | Station type lightning arrestor complete with steel support structures. | |
| 2. | Type | Zinc oxide gapless lightning arrestor | |
| System parameters | |||
| 3. | Nominal system voltage | kV | 66 |
| 4. | Highest system voltage | kV | 72.5 |
| 5. | Power frequency | Hz | 50 |
| 6. | Type of system earthing | Effective/Non effective | |
| 7. | Type of arrestor connection to system | Line to ground | |
| 3. Ratings and type of surge arrester | |||
| 8. | Rated voltage of surge arrester | kV rms | 54 |
| 9. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA peak | 10 |
| 10. | Maximum continuous operating voltage of surge arrester | kV | 43 |
| 11. | Minimum one minute wet power frequency withstand voltage | kVrms | 140 |
| of external insulation of surge arrester housing | |||
| 12. | Maximum steep current impulse residual voltage for a 2 kA, 30/60 µs, discharge current | kVpeak | 104 |
| 13. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current | kVpeak | 127 |
| 14. | Minimum lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing | 325 | |
| 15. | Line discharge class rating | 2 | |
| 16. | Lighting arrestor counter, leakage current meter and their accessories to be provided | Yes/No | Yes |
| 17. | Gapless or gapped type metal-oxide surge arrester | Gapless | |
| 18. | Insulation Material | Porcelain | |
| 19. | Cantilever strength of surge arrester | Nm | 3000 |
| 20. | Rated frequency of surge arrester | Hz | 50 |
| 21. | Maximum angle from vertical at which surge arrester is fully functional | Deg | 45 |
| 22. | Design altitude of surge arrester (above sea level) | m | 1400 m |
| 23. | Design ambient temperature of surge arrester | oC | -1 to 40 |
| 24. | Humidity | % | 85 |
| 25. | Specific phase-to-ground creepage of surge arrester | .mm/kV | 25 |
| 26. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade | to SABS 763 or 316 stainless steel | |
| 27. | Previous type test results/certificate to be provided with bid | Yes/No | Yes |
| 28. | Design drawings showing dimensions including foundations and brochures to be provided with bid | Yes/No | Yes |
| 29. | Quality Assurance certification to be provided with the bid | Yes/No | Yes |
| 30. | Routine test results/certificate to be provided on delivery | Yes/No | Yes |
| 31. | Galvanized steel support structures complete with bolts & washers to be provided on delivery | Yes/No | Yes |
| 32. | Applicable standard | IEC60099 |
| S/N | TECHNICAL DETAILS | UNITS | DATA |
| 33. | Description | Station type lightning arrestor complete with steel support structures. | |
| 34. | Type | Zinc oxide gapless lightning arrestor | |
| System parameters | |||
| 35. | Nominal system voltage | kV | 88 |
| 36. | Highest system voltage | kV | 100 |
| 37. | Power frequency | Hz | 50 |
| 38. | Type of system earthing | Effective/Non effective | |
| 39. | Type of arrestor connection to system | Line to ground | |
| 3. Ratings and type of surge arrester | |||
| 40. | Rated voltage of surge arrester | kV rms | 84 |
| 41. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA peak | 10 |
| 42. | Maximum continuous operating voltage of surge arrester | kV | 67 |
| 43. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing | kVrms | 185 |
| Maximum steep current impulse residual voltage for a 2 kA, | kVpeak | 188 | |
| 30/60 µs, discharge current | |||
| 45. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current | kVpeak | 218 |
| 46. | Minimum lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing | 450 | |
| 47. | Line discharge class rating | 2 | |
| 48. | Lighting arrestor counter, leakage current meter and their accessories to be provided | Yes/No | Yes |
| 49. | Gapless or gapped type metal-oxide surge arrester | Gapless | |
| 50. | Insulation Material | Porcelain | |
| 51. | Cantilever strength of surge arrester | Nm | 3000 |
| 52. | Rated frequency of surge arrester | Hz | 50 |
| 53. | Maximum angle from vertical at which surge arrester is fully functional | Deg | 45 |
| 54. | Design altitude of surge arrester (above sea level) | m | 1400 m |
| 55. | Design ambient temperature of surge arrester | oC | -1 to 40 |
| 56. | Humidity | % | 85 |
| 57. | Specific phase-to-ground creepage of surge arrester | .mm/kV | 25 |
| 58. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade | to SABS 763 or 316 stainless steel | |
| 59. | Previous type test results/certificate to be provided with bid | Yes/No | Yes |
| 60. | Design drawings showing dimensions including foundations and brochures to be provided with bid | Yes/No | Yes |
| 61. | Quality Assurance certification to be provided with the bid | Yes/No | Yes |
| 62. | Routine test results/certificate to be provided on delivery | Yes/No | Yes |
| 63. | Galvanized steel support structures complete with bolts & washers to be provided on delivery | Yes/No | Yes |
| 64. | Applicable standard | IEC60099 |